ZORC Switching Surge Suppressors for Motors and Transformers

High Frequency Transient Surge Suppressors
For protection of medium and low voltage motors and transformers

Zorc Surge Suppressor

Every year huge losses are incurred by end-users because of insulation failures of medium voltage (3kV – 40kV) motors, and dry-type transformers. This can be caused by:

  • Switching transients associated with vacuum and other switchgear resulting in expensive insulation failures of motors and dry-type transformers.
  • Multiple pre-striking and re-striking (re-ignition) at the motor or transformer terminals.

ZORC is a patented network of capacitors, resistors and zinc-oxide (ZnO) arresters that eliminates multiple pre-strike and re-strike transients from vacuum and other switchgear. It is designed and manufactured in South Africa by Strike Technologies.

The ZORC surge suppressor is a unique high frequency transient over voltage surge suppressor for the protection of motors and transformers from steep wave-front, short rise-time, high magnitude, spikes, surges and other transient voltages, generated by switching, lightning and other sources.

button_inquire_now

Download: ZORC operating manual (PDF)

Characteristics

The protective characteristics of ZORC units:

  • Eliminates inter-turn insulation failures
  • Extends the life of machine insulation
  • Provides comprehensive insulation co-ordination at all practical surge magnitudes and rise-times
  • Conforms with both the CIGRE and IEEE motor impulse voltage withstand recommendations
  • Halves the magnitude of steep wave-front surges impinging on the load terminals by providing a matched cable terminating impedance under transient conditions, thereby eliminating refraction of steep wave-front surges (i.e. eliminates voltage doubling effects).
  • Eliminates multiple pre-striking and re-striking transients associated with vacuum and other switchgear, by eliminating reflections of the pre-strike and re-strike current wave-fronts, and thus preventing high frequency current zeros in the contact gap of the switch.

Applications

Installed in the following industries:

  • Chemical
  • Petrochemical
  • Underground mining (gold, platinum, coal, other)
  • Surface mining (coal, copper, uranium, iron ore, other)
  • Metal beneficiation (steel, stainless steel, gold, platinum, copper and uranium refineries)
  • Power generation (generators, power station auxiliaries)
  • Pumping (water pumping stations, oil pipelines)

Applied

Specific applications on medium voltage motors, generators, and dry-type and oil immersed transformers include:-

  • Fans
  • Pumps
  • Compressors
  • Mills
  • Crushers
  • Refrigeration machines
  • Motor-generator sets
  • Mine winders
  • Conveyors
  • Underground and surface mini-substations and mobile substations
  • Generators
  • Power station auxiliaries
  • Induction & arc furnaces
button_inquire_now

Benefits

Benefits provided by ZORC units :

  • Saves money by eliminating production downtime incurred due to insulation failures of motors and dry-type transformers.
  • Protects new motors and dry-type transformers throughout their service life.
  • Extends the life of motor and dry-type transformer insulation if retrofitted to existing motors and dry-type transformers in service.

Features

ZORC Models to suit various voltages : 400V to 40kV.

ZORC units

  • Available in single phase and three phase units. Single-phase versions are suitable for installing in phase segregated terminal enclosures.

Compact and easy to install

  • Special compact versions that can be fitted within most motor/transformer terminal enclosures or switchgear panels.

ZORC models and voltage ratings

RangeModelsSystem voltageMounting
Standard, three-phaseM3-3kV, M3-6kV, M3-11kV (machine)
P3-3kV, P3-6kV, P3-11kV (panel)
3–3.6 kV, 6–7.2 kV, 10–12 kV, 50/60 HzMotor/transformer terminal box (M) or switchgear panel (P)
Single-phaseM1-3kV, M1-6kVOther voltages on requestPhase-segregated terminal enclosures
CompactM3C-3kV, M3C-6kV3.3 kV and 6.6 kVInside the terminal box, with 1 m flexible silicone leads
Low voltageLVZ400, LVZ550, LVZ1100380/400 V, 525/550 V, 1000/1100 V, 50 HzMachine or panel
Custom RC suppressorsOn request15/24 kV and 30/36 kVDry-type and arc furnace transformers

Ordering example: ZORC type M3-11KV-EXN = machine mount, three-phase, 11 kV, ExN (non-sparking) certified. Panel-mount units are available up to 13.8 kV; machine-mount units up to 40 kV.

Key technical data

ParameterValue
RC circuit (standard three-phase)0.2 µF capacitor and 30 Ω non-inductive resistor per phase
Time constantτ = RC = 6 µs
MOV / ZnO arrester reaction timeLess than 25 ns
Arrester trigger (knee-point) voltage1–2 pu (machine mount), 0.5–1 pu (panel mount)
Capacitive reactance to earth≈ 16 kΩ at 50 Hz, ≈ 13 kΩ at 60 Hz
StandardsIEC 60871-1, ANSI/IEEE 18, NEMA CP-1, VDE 0560 part 410, CIGRE 13.02
Hazardous areas (option)Class 1 Division 2 (ExN non-sparking), temperature classes T1 to T5
Expected lifeApprox. 20 years under normal operating conditions
TestingEvery unit routine tested before dispatch; test certificates available

Installation guidelines

  • Mount the ZORC no more than 20 m (supply cable length) from the machine or switchgear.
  • Keep the cable from the ZORC to the machine terminals or busbar under 5 m; 3 m is strongly recommended.
  • Connection cable: minimum 2.5 mm² for 3.3–13.8 kV units, 4 mm² for 15–22 kV, 6–10 mm² for 25–40 kV.
  • Earth cable: 16–25 mm², braided copper preferred, connected to the earth of the machine or switchgear panel it protects.
  • Tighten bushing terminal nuts to 20 Nm or less, and insulate the bushing terminals (tape or insulator caps).
  • The ZORC can be mounted in any orientation, but must not be exposed directly to motor or generator vibration.
  • Harmonics heat the unit: a total harmonic voltage distortion of 8% or more should be considered dangerous to the ZORC.

ZORC frequently asked questions

Does the ZORC protect against lightning?

No. The ZORC is designed for switching transients, not direct lightning strikes. Use additional lightning protection in high-lightning areas.

How do I select the right ZORC?

Match the ZORC to the system line-to-line voltage, and decide whether it will be mounted at the machine or in the switchgear panel. Machine mounting gives the best protection.

What maintenance does a ZORC need?

It is maintenance-free apart from cleaning the bushings in contaminated areas. Visual inspections every two months and an electrical test once a year are recommended, and testing can be done without a shutdown.

Is the ZORC a power factor correction capacitor?

No. It is a high-frequency transient overvoltage surge suppressor and must not be used for power factor correction.

How does the ZORC differ from a plain RC suppressor?

Below the arrester knee-point voltage it works as a normal RC suppressor. Above it, the arresters effectively leave only the capacitor in circuit, which slopes the wave-front and attenuates the transient further.

Related products

Downloads

Get a ZORC quote

Tell us your system voltage, the equipment you need to protect and whether you need machine or panel mounting, and we will recommend the right ZORC surge suppressor.

Supplier: Access TD Beyrouthi Family (ABN 21 418 290 162), PO Box 3768, Australia Fair QLD 4215, Australia. Contact us.